Ex d position transmitter
Fast, high-resolution 4-20 mA position feedback for rotary actuators, with HART 7.
HYTRACK measures rotary position up to 360° with a 12-bit contactless sensor and reports it on a two-wire, loop-powered 4-20 mA signal. Limit switches, a mechanical indicator and HART are options, all in a flameproof 316L stainless steel housing.

12bit
Contactless sensorNo wear on the measuring element.
20ms
Output responseSampling every 150 μs.
360°
Rotary rangeEnd positions set in two steps.
IP66
Ingress protectionNEMA 4X, in 316L stainless steel.
Overview
HYTRACK is our feedback transmitter. It delivers fast, high-resolution position data for most rotary actuators, from on-off valves to modulating duties, and suits harsh sites thanks to its rugged 316L enclosure.
It mounts on a NAMUR shaft with F05 and F08 ISO 5211 patterns. Magnetic buttons set it up through the closed lid, so the flameproof enclosure stays intact, and the display shows position in percent or milliamps.
HYTRACK comes fitted to our own actuators or as a standalone transmitter for other rotary actuators, and it is built into HYCONTROL A-HCR positioners.
At a glance
Set up in minutes
Calibration takes two steps: move the valve to one end and confirm, then the other. From the same menu you can reverse the signal or trim the 4 mA and 20 mA points, all with magnetic buttons through the closed lid.

Advantages
A compact transmitter that keeps feedback accurate, wiring simple and the enclosure sealed.

A 12-bit sensor with no mechanical wear, for reliable, precise feedback over a long service life.
Sampling every 150 μs for a 20 ms output response, with hysteresis below 0.048%.
4-20 mA, 24 V DC, two-wire loop-powered.
Digital communication for diagnostics, using a generic device description.
Magnetic buttons configure the unit without opening the flameproof enclosure.
A 128 x 64 pixel LCD shows position in percent or milliamps.
Two or four mechanical or proximity switches, NAMUR compatible where applicable.
An optional visual indicator for rotary actuators, with custom options.
IP66 and NEMA 4X, for offshore and corrosive environments.
Technical data
Specifications from the HYTRACK data sheet. Each unit's configuration and certification are confirmed when you order.
| Property | HYTRACK |
|---|---|
| Type | Ex d 4-20 mA position transmitter, A-HR |
| Sensor | 12-bit contactless |
| Measuring range | Rotary, 0 to 360°, end positions set at calibration |
| Output | 4-20 mA, two-wire loop-powered; HART 7 digital option |
| Operating voltage | 24 V DC |
| Maximum load | 500 Ω |
| Sampling rate | 150 μs |
| Output response time | 20 ms |
| Hysteresis | Below 0.048% |
| Limit switches | Two or four; mechanical (standard) or proximity |
| Display | LCD, 128 x 64 pixels |
| Housing | 316L stainless steel |
| Ingress protection | IP66 and NEMA 4X |
| Ambient temperature | -40 °C to +70 °C |
| Storage temperature | -40 °C to +100 °C |
| Cable entries | 3 x M20 x 1.5; option 3 x ½ inch NPT |
| Mounting | NAMUR shaft, F05 and F08 to ISO 5211 |
| Dimensions | Ø150 mm x 135 mm |
| Weight | Approximately 9 kg |
Model codes run from A-HR-S2M3, with two mechanical switches, to A-HR-FS4P3VM, with 4-20 mA, four proximity switches and an indicator. Other configurations are available on request.
| Feedback | Switch type | Switches | Mechanical indicator |
|---|---|---|---|
| Switches only | Mechanical or proximity | Two or four | Optional |
| 4-20 mA and switches | Mechanical or proximity | Two or four | Optional |
| Property | HYTRACK |
|---|---|
| Signal | 4-20 mA with HART digital |
| HART revision | 7 |
| Universal commands | Supported |
| Device description | Generic only; no specific DD needed |
The certificates cover the A-H* flameproof enclosure used by HYTRACK, HYCONTROL and HYDRIVE.
| Scheme | Certificate and marking |
|---|---|
| ATEX | ExVeritas 22 ATEX 1354 X, issue 3 |
| UKEX | ExVeritas 22 UKEX 1355 X, issue 3 |
| IECEx | IECEx EXV 22.0040X, issue 3, February 2026 |
| INMETRO | CPEx 24.1587 X |
| Gas marking | II 2 G Ex db IIC T6 to T4 Gb |
| Dust marking | II 2 D Ex tb IIIC T85 °C to T135 °C Db |
From the certificate schedules. The lowest ambient is -40 °C in every class.
| Gas and dust class | Maximum ambient |
|---|---|
| T6, T85 °C | +50 °C |
| T5, T100 °C | +70 °C |
| T4, T135 °C | +105 °C, or +90 °C with a glass window lid |
Sources: HYTRACK A-HR data sheet, October 2026, and installation manual, Advanced Actuators; ExVeritas ATEX and UKEX, IECEx and INMETRO certificates. Specifications vary with configuration; each unit is confirmed when you order.
3D model
Rotate, zoom and explode a representative HYTRACK to see the housing, sensor, display and shaft.
The model only loads when you ask for it.
Valves and applications
HYTRACK gives position feedback on quarter-turn valves, on our actuators and on other rotary actuators with NAMUR mounting.
Quarter-turn valvesChoke valvesRotary actuatorsNAMUR mounting
Need closed-loop control as well? HYCONTROL A-HCR has HYTRACK built in: see HYCONTROL positioners.
Hazardous area? Tell us the zone, gas group and temperature class, and we will confirm the certification for your exact unit.
Feedback on choke, control and isolation valves, onshore and offshore.
Flameproof and dust-protected, to equipment protection levels Gb and Db.
Fitted to HYSTEP, HYLINE and HYLINE-R, and to other rotary actuators with NAMUR mounting.
Adds 4-20 mA and HART feedback to rotary actuators already in service.
Certification
Certified for hazardous areas under ATEX, UKEX, IECEx and INMETRO, with the certificates listed in the technical data. Tell us what your project calls for and we will confirm the marks for your unit when we quote.









Downloads
Sizing help
Send the actuator make and mounting, the signals and switches you need, and the area classification, and we will confirm the model.
Already installed
Overhaul, repair and spares for actuators in service, with commissioning support on site.
Size your HYTRACK
We just need three details.
Replacing one? Send the model code from the nameplate and a photo, and we will work from those.
Make, model and mounting, or the Advanced Actuators range it will fit.
4-20 mA, HART, and how many limit switches.
Area classification, cable entries and whether you need an indicator.
Email us your detailsCall +44 (0)1535 655151
Prefer us to call you? Request a callback.
It measures the rotary position of an actuator or valve and reports it as a 4-20 mA signal, with optional HART 7 and limit switches.
In two steps: set position 1 at one end of travel, then position 2 at the other, using the magnetic buttons. You can also reverse the output or trim the 4 mA and 20 mA points.
No separate power supply is needed. HYTRACK is powered by its 4-20 mA, 24 V DC two-wire loop.
Two or four switches, mechanical as standard or non-contact proximity, with or without the 4-20 mA output.
HYTRACK mounts on a NAMUR shaft with F05 and F08 ISO 5211 patterns. Send us the actuator details and we will confirm.
ATEX 22 ATEX 1354 X, UKEX 22 UKEX 1355 X, IECEx EXV 22.0040X and INMETRO CPEx 24.1587 X, marked Ex db IIC Gb and Ex tb IIIC Db. The temperature class depends on the maximum ambient.
Yes, HART revision 7 as a digital option on the 4-20 mA output, using a generic device description.
Yes. HYCONTROL A-HCR positioners have HYTRACK feedback built in. See HYCONTROL.