Home›Products›HYCONTROL

Ex d valve positioner

HYCONTROL Valve Positioners

Closed-loop positioning, diagnostics and HPU control for hydraulic and pneumatic actuators.

HYCONTROL positions modulating valves from a 4-20 mA command, driving suitable solenoid valves or a DC reversing motor, and can run the hydraulic pump as well. The A-HCR version has HYTRACK feedback built in, all in a flameproof 316L stainless steel housing.

Get a priceDownload the data sheet

HYCONTROL valve positioner with display and a stainless steel Ex terminal box

4-20mA

Command and feedbackIsolated, with a 4-20 mA retransmit.

HART 7

Digital communicationAlongside analogue and digital in and out.

3ways

To fail safeFail open, fail close or stay put.

IP66

Ingress protectionNEMA 4X, in 316L stainless steel.

Overview

One controller for the whole loop

HYCONTROL is an intelligent position controller. It provides closed-loop control, accurate valve positioning, actuator diagnostics and HPU control for modulating valves on hydraulic or pneumatic actuators.

It works with double-acting and spring-return actuators, through solenoid valves or a DC reversing motor. Stepping mode, dead and pulsing zones and selectable fail actions let it suit the valve and the duty, and the graphic display shows status and position behind the enclosure window.

On hydraulic packages it can also control the pump, on pressure or on demand, and it monitors and logs faults such as oil level, oil temperature and accumulator pressure.

Choose HYCONTROL for

  • Modulating control valves on hydraulic or pneumatic actuators
  • Hydraulic packages where the positioner also runs the pump
  • Duties that need a defined fail action on signal loss
  • Hazardous areas, with ATEX, UKEX, IECEx and INMETRO certificates

At a glance

HYCONTROL

Type
Ex d positioner, A-HC and A-HCR
Command
4-20 mA, isolated
Feedback
4-20 mA or integral sensor
Communication
HART 7
Drive
Solenoid valves or DC motor
Fail action
Open, close or stay put
Housing
316L, IP66, NEMA 4X
Ambient
-40 °C to +50 °C

Closed loop

Command in, position out

HYCONTROL takes the 4-20 mA command from your control system, drives the actuator to match it and checks the result against the valve position. It reports back with a 4-20 mA retransmit and fault relays, so the control room always knows where the valve is.

HYCONTROL closed loop: a 4-20 mA command in, drive outputs to the actuator, position feedback back, and a 4-20 mA retransmit and fault relays to the control systemControl systemDCS or PLCHYCONTROLA-HC, or A-HCR with HYTRACKDriveSolenoid valves, DC motor or HPU pumpActuator and valveHydraulic or pneumatic4-20 mA commandDrive outputsHydraulic or pneumatic powerPositionfeedback4-20 mA out,fault relays
Where HYCONTROL sits in the control loop. On A-HCR, the position feedback comes from the built-in HYTRACK.
  • A-HCThe positioner, with its integral rotary sensor or a 4-20 mA input
  • A-HCRThe positioner with HYTRACK feedback built in
  • HPU controlPump speed signal and pump control on pressure or demand

Advantages

Why choose HYCONTROL

A positioner built for hydraulic and pneumatic actuators, with the safety and monitoring modulating packages need.

Exploded view of a HYCONTROL valve positioner, showing the display head and terminal box

Two-step calibration

Simple calibration and manual operation from magnetic buttons, without opening the enclosure.

Stepping mode

Adjustable on and off times for fine, stepped positioning.

Selectable fail action

Fail open, fail close or stay put, with the solenoid drive sense chosen at setup.

Signal-break response

Selectable behaviour when the command or feedback signal is lost.

HPU control

Runs the hydraulic pump on pressure or on demand, with a 0-5 V speed signal.

Fault monitoring

Oil level, oil temperature, accumulator pressure, motor and pump faults, with logging.

Fault relays

Two changeover relay outputs and three isolated digital inputs.

Built-in feedback

A-HCR carries a HYTRACK transmitter, so one unit does both jobs.

316L stainless steel

IP66 and NEMA 4X, with an optional stainless Ex terminal box.

Technical data

HYCONTROL technical specifications

Specifications from the HYCONTROL data sheet and manual. Each unit's configuration and certification are confirmed when you order.

General data

PropertyHYCONTROL
TypeEx d closed-loop positioner: A-HC, or A-HCR with HYTRACK feedback built in
DriveSuitable solenoid valves or a DC reversing motor
ActuatorsDouble-acting, spring to close or spring to open; hydraulic or pneumatic
Command signal4-20 mA, isolated (5 V voltage drop)
Valve feedback4-20 mA or the integral rotary sensor, isolated
Retransmitted signal4-20 mA, externally loop powered
CommunicationHART 7
Power supply24 V DC, 0.1 A (17 to 30 V DC)
Digital inputs3 x 24 V DC, isolated, for oil and fault monitoring
Relay outputs2 x changeover contacts, 24 V, 1 A
Solenoid outputs24 V DC, 1 A, low-side switching
Pump speed signal0-5 V DC
Hydraulic pump controlOn pressure or on demand
Dead zone0 to 5%
Pulsing zone0 to 10%
Action on signal lossFail open, fail close or stay put
DisplayGraphic LCD behind the enclosure window
Housing316L stainless steel; optional 316 stainless steel Ex terminal box
Ingress protectionIP66 and NEMA 4X
Ambient temperature-40 °C to +50 °C
Storage temperature-40 °C to +100 °C
Cable entries3 x M20 x 1.5; option 3 x ½ inch NPT
DimensionsØ150 mm x 135 mm (head)
WeightApproximately 10 kg

Configurations

Entry and terminal-box options are chosen separately, shown as -XXX in the model code.

ModelFunctionSwitch typeSwitchesMechanical indicator
A-HCController and switchesMechanical or proximityTwo or fourYes
A-HCRController, HYTRACK feedback and switchesMechanical or proximityTwo or fourYes

Head options

CodeDescription
A-HCH3MHead only, 3 x M20 entries
A-HCH3NHead only, 3 x ½ inch NPT entries
A-HCH3MBHead with a 316 stainless steel Ex terminal box

Hazardous-area certification

The certificates cover the A-H* flameproof enclosure used by HYCONTROL, HYTRACK and HYDRIVE.

SchemeCertificate and marking
ATEXExVeritas 22 ATEX 1354 X, issue 3
UKEXExVeritas 22 UKEX 1355 X, issue 3
IECExIECEx EXV 22.0040X, issue 3, February 2026
INMETROCPEx 24.1587 X
Gas markingII 2 G Ex db IIC T6 to T4 Gb
Dust markingII 2 D Ex tb IIIC T85 °C to T135 °C Db

Temperature class by maximum ambient

From the certificate schedules. HYCONTROL's own ambient range is -40 °C to +50 °C.

Gas and dust classMaximum ambient
T6, T85 °C+50 °C
T5, T100 °C+70 °C
T4, T135 °C+105 °C, or +90 °C with a glass window lid

Sources: HYCONTROL A-HC and A-HCR data sheet, July 2026, and A-HC installation and operation manual, Advanced Actuators; ExVeritas ATEX and UKEX, IECEx and INMETRO certificates. Specifications vary with configuration; each unit is confirmed when you order.

Options

Configure your HYCONTROL

Choose the model, the switches and the head; the controller and housing stay the same.

A-HC or A-HCR

The positioner alone, or with HYTRACK position feedback built in.

Switch type

Mechanical or non-contact proximity switches.

Switch quantity

Two or four switches.

Mechanical indicator

A visual position indicator for rotary actuators.

Head and entries

Three M20 or three ½ inch NPT entries, or a 316 stainless steel Ex terminal box.

Drive

Solenoid valves, a DC reversing motor, or pump control for an HPU.

3D model

Take a HYCONTROL apart in 3D

Rotate, zoom and explode a representative HYCONTROL to see the housing, controller and display.

Load the 3D model

The model only loads when you ask for it.

Valves and applications

Where HYCONTROL works

HYCONTROL suits modulating control valves operated by hydraulic or pneumatic actuators.

Control valvesChoke valvesLinear actuatorsRotary actuators

Only need feedback? See HYTRACK position transmitters.

Hazardous area? Tell us the zone, gas group and temperature class, and we will confirm the certification for your exact unit.

  • Oil and gas

    Modulating control on hydraulic and pneumatic valve packages, onshore and offshore.

  • Electro-hydraulic packages

    Positioning and pump control together, for self-contained hydraulic units.

  • Hazardous areas

    Flameproof and dust-protected, to equipment protection levels Gb and Db.

  • Our actuators

    Pairs with HYLINE, HYLINE-R, HYSTEP and HYFLOW for complete packages.

Certification

Specified to suit your project

Certified for hazardous areas under ATEX, UKEX, IECEx and INMETRO, with the certificates listed in the technical data. Tell us what your project calls for and we will confirm the marks for your unit when we quote.

ISO 9001 certified quality managementISO 45001 certified health and safety managementEx mark for equipment for explosive atmospheresIECEx certification schemeUKCA markingINMETRO certification for BrazilIP66 ingress protection ratingIP68 ingress protection ratingNEMA 4X enclosure rating

Downloads

HYCONTROL downloads

  • HYCONTROL data sheet

    PDF, 2.0 MB. Specifications, dimensions, markings and configurations.

    Download

  • Controls and instrumentation flyer

    PDF, 1.6 MB. HYCONTROL with the rest of our instrumentation.

    Download

  • Technical library

    Manuals, declarations and Ex certificates, on our document library.

    Download

Sizing help

Not sure which size?

Send the actuator type, the drive, the fail action and the signals you need, and we will confirm the model.

Already installed

Servicing and repairs

Overhaul, repair and spares for actuators in service, with commissioning support on site.

Size your HYCONTROL

Looking for a HYCONTROL or a price?

We just need three details.

Replacing one? Send the model code from the nameplate and a photo, and we will work from those.

  1. Actuator

    Hydraulic or pneumatic; double-acting, spring to close or spring to open.

  2. Drive and signals

    Solenoids, DC motor or HPU pump; 4-20 mA, HART and switches.

  3. Site

    Area classification, cable entries and whether you need a terminal box.

Email us your detailsCall +44 (0)1535 655151

Prefer us to call you? Request a callback.

FAQs

HYCONTROL questions

Anything else? Call +44 (0)1535 655151 or email sales@advanced-actuators.com.

What does HYCONTROL do?

It is a closed-loop positioner: it takes a 4-20 mA command, drives the actuator through solenoid valves or a DC reversing motor, and checks the valve position until they match.

What is the difference between A-HC and A-HCR?

A-HC is the positioner. A-HCR has a HYTRACK position transmitter built in, so one unit provides control and feedback.

Which actuators can it control?

Hydraulic and pneumatic actuators: double-acting, single-acting spring to close and single-acting spring to open.

Can it control a hydraulic pump?

Yes. It can run the pump on pressure or on demand, with a 0-5 V DC speed signal, and it monitors oil level, oil temperature, accumulator pressure, motor and pump faults.

What happens if the signal is lost?

You choose at setup: fail open, fail close or stay put, with selectable behaviour on command or feedback signal break.

Is HART supported?

Yes. HYCONTROL offers 4-20 mA control and feedback with HART 7, alongside analogue and digital inputs and outputs.

Which hazardous-area certificates does it hold?

ATEX 22 ATEX 1354 X, UKEX 22 UKEX 1355 X, IECEx EXV 22.0040X and INMETRO CPEx 24.1587 X, marked Ex db IIC Gb and Ex tb IIIC Db. The temperature class depends on the maximum ambient.

How is it set up?

With a simple two-step calibration using magnetic buttons, so the flameproof enclosure stays closed. Manual operation is available from the same buttons.