Quarter-turn electric
On-off, modulating or intelligent control. 50 Nm to 6,000 Nm. Standard HYLINE-E or heavy-duty HYLINE-EQ.
HYLINE-E turns ball, butterfly and plug valves and dampers through a self-locking worm gear that holds position when power is removed. For demanding process environments, HYLINE-EQ adds a double worm gear, a de-clutchable handwheel, over-torque switches and a wider choice of enclosures.

6,000Nm
Peak torqueBoth ranges reach 6,000 Nm.
2ranges
Standard and heavy-duty13 HYLINE-E sizes from 50 Nm, 14 HYLINE-EQ sizes from 60 Nm.
3controls
On-off, modulating, intelligent4-20 mA command and feedback on modulating units.
IP67
Standard enclosureIP68 available on both ranges.
Overview
A motor-driven worm gear turns the valve through 90°, and the self-locking gear train holds it in place when power is removed. No air or hydraulic supply is needed: just mains or DC power and a control signal.
HYLINE-E is the standard range: 13 sizes from 50 Nm to 6,000 Nm on single or three phase AC, or DC up to ATE-200, with on-off, modulating and intelligent control. HYLINE-EQ is built for heavier process duty, with 14 sizes from 60 Nm to 6,000 Nm, a hard anodised and epoxy-coated housing, an integral space heater, and battery or spring-return fail-safe options.
Our established ranges already cover the vast majority of quarter-turn duties. Where yours is genuinely different, we engineer the mounting, controls or package around it.
At a glance
Two ranges
Both ranges cover the same torque band, so the choice comes down to the job. HYLINE-E suits general automation with frequent operation. HYLINE-EQ suits heavy process duty, harsh sites and fail-safe needs.
Advantages
Simple, self-contained electric actuation, with the control and enclosure options to suit the valve, the signal and the site.

The worm gear holds valve position when power is removed, with no brake needed.
Detachable crank handle on HYLINE-E; de-clutchable handwheel on HYLINE-EQ.
Squirrel cage induction motors, Class F insulated on HYLINE-E and built for high starting torque on HYLINE-EQ.
Built-in thermal protection guards the motor against overheating.
A heater is standard, keeping the enclosure dry in humid and outdoor sites.
Standard on HYLINE-EQ (from ATQ-160) and available on HYLINE-E, to stop the actuator on a mechanical overload.
IP68 available on both ranges; HYLINE-EQ is tested to 30 m for 24 hours.
On-off, modulating and intelligent, with fieldbus on request for HYLINE-EQ.
HYLINE-EQ offers battery backup or a spring-return module where a valve must move on loss of power.
Technical data
HYLINE-E in 13 sizes and HYLINE-EQ in 14. Choose the first size with an output torque above your valve torque plus a safety factor of at least 20%, and check the stem and ISO 5211 pattern match the valve.
| Property | HYLINE-E | HYLINE-EQ |
|---|---|---|
| Torque range | 50 Nm to 6,000 Nm | 60 Nm to 6,000 Nm |
| Sizes | 13 | 14 |
| Gear drive | Self-locking worm gear, heat-treated alloy steel | Double worm gear, self-locking without a brake |
| Motor | Squirrel cage induction motor, Class F insulation | Heavy-duty squirrel cage induction motor, high starting torque |
| Power | 1 phase 110 or 220 V AC; 3 phase 380 or 440 V AC (±10%, 50/60 Hz); 12, 24 or 48 V DC up to ATE-200 | Standard: 1 phase 220 V AC, 3 phase 380 V AC. Options: 1 phase 110 V AC, 3 phase 220 or 440 V AC, 24 V AC, 24 V DC |
| Duty, on-off | S2, 30 min | S2, 15 min at 380 V AC; S2, 10 min at 220 V AC |
| Duty, modulating | S4, 40%, up to 1,200 starts per hour | S4, 25%, up to 600 starts per hour |
| Control | On-off; modulating 4-20 mA or 2-10 V; intelligent with local control unit | On-off; modulating 4-20 mA; local control unit with LED or LCD display |
| On loss of power | Stays in last position | Stays in position; battery backup or spring-return fail-safe options |
| On loss of signal | 4-20 mA and 2-10 V: open or closed, selectable; 0-10 V: closes | Not listed |
| Manual override | Detachable crank handle; handwheel option | De-clutchable handwheel |
| Switches | Limit switches at each end of travel; torque switch option (ATE-10 to ATE-300) | 2 limit and 1 over-torque switch at each end, 5 A at 250 V AC (no torque switches on ATQ-060 and ATQ-100) |
| Enclosure | IP67 standard; IP68 option | Weatherproof IP67 and NEMA 4 and 6; IP68 (30 m for 24 hours) and Ex d explosion-proof options |
| Cable entry | On-off: 1 x M20 x 1.5; modulating and intelligent: 2 x M20 x 1.5 | 2 x 3/4" NPT |
| Ambient temperature | -25 °C to +70 °C; option -40 °C to +65 °C | -20 °C to +70 °C; options to -40 °C or -60 °C |
| Protection | Heater and built-in thermal protector, auto-reset at 125 °C | 5 W anti-condensation heater; thermal protection opens at 150 °C, closes at 97 °C |
| Valve mounting | ISO 5211 | ISO 5211, removable drive bushing |
| Fieldbus | Not listed | CANbus, Modbus, PROFIBUS or HART on request |
Operating time for 0-90° on AC supplies. Weight for on-off, modulating and intelligent versions.
| Model | Torque Nm | Time s | Motor W | Stem mm | ISO 5211 | On-off kg | Modulating kg | Intelligent kg |
|---|---|---|---|---|---|---|---|---|
| ATE-05 | 50 | 30 | 10 | 14 x 14 | F03 / F05 / F07 | 3.0 | 3.0 | 6.5 |
| ATE-10 | 100 | 20 | 30 | 17 x 17 | F05 / F07 | 4.5 | 4.5 | 8.0 |
| ATE-16 | 160 | 30 | 30 | 17 x 17 | F05 / F07 | 4.5 | 4.5 | 8.0 |
| ATE-25 | 250 | 30 | 40 | 22 x 22 or 27 x 27 | F07 / F10 / F12 | 9.8 | 10.0 | 12.3 |
| ATE-40 | 400 | 30 | 60 | 22 x 22 or 27 x 27 | F07 / F10 / F12 | 9.8 | 10.0 | 12.3 |
| ATE-60 | 600 | 30 | 90 | 22 x 22 or 27 x 27 | F07 / F10 / F12 | 9.8 | 10.0 | 12.3 |
| ATE-100 | 1,000 | 30 | 150 | 27 x 27 or 36 x 36 | F10 / F12 or F10 / F14 | 14.5 | 14.7 | 18.0 |
| ATE-160 | 1,600 | 50 | 150 | 27 x 27 or 36 x 36 | F10 / F12 or F10 / F14 | 14.5 | 14.7 | 18.0 |
| ATE-200 | 2,000 | 60 | 150 | 27 x 27 or 36 x 36 | F10 / F12 or F10 / F14 | 14.5 | 14.7 | 18.0 |
| ATE-250 | 2,500 | 50 | 200 | 27 x 27 or 36 x 36 | F14 or F12 / F16 | 24.9 | 25.1 | 28.4 |
| ATE-300 | 3,000 | 60 | 200 | 27 x 27 or 36 x 36 | F14 or F12 / F16 | 24.9 | 25.1 | 28.4 |
| ATE-400 | 4,000 | 100 | 200 | 36 x 36 or 46 x 46 | F16 or F25 | 43.5 | 43.7 | 47.0 |
| ATE-600 | 6,000 | 150 | 200 | 36 x 36 or 46 x 46 | F16 or F25 | 57.1 | 57.3 | 60.6 |
Operating time at 50 Hz and 60 Hz. Maximum bore for a square drive and for a keyed shaft.
| Model | Torque Nm | ISO 5211 | Time 50 / 60 Hz s | Bore, square mm | Bore, keyed mm | Weight kg | Handwheel turns |
|---|---|---|---|---|---|---|---|
| ATQ-060 | 60 | F05 / F07 | 26 / 22 | 17 | Ø22 | 8 | 10 |
| ATQ-100 | 100 | F05 / F07 | 26 / 22 | 17 | Ø22 | 8 | 10 |
| ATQ-160 | 160 | F07 / F10 | 28 / 23 | 22 | Ø32 | 14 | 12 |
| ATQ-200 | 200 | F07 / F10 | 28 / 23 | 22 | Ø32 | 14 | 12 |
| ATQ-240 | 240 | F07 / F10 | 28 / 23 | 22 | Ø32 | 14 | 12 |
| ATQ-350 | 350 | F10 / F12 | 32 / 27 | 22 | Ø32 | 18 | 13 |
| ATQ-500 | 500 | F10 / F12 | 32 / 27 | 22 | Ø32 | 19 | 13 |
| ATQ-800 | 800 | F12 or F14 | 36 / 30 | 36 | Ø42 | 24 | 15 |
| ATQ-1100 | 1,100 | F12 or F14 | 36 / 30 | 37 | Ø42 | 26 | 15 |
| ATQ-1500 | 1,500 | F14 or F16 | 55 / 46 | 46 | Ø60 | 50 | 46 |
| ATQ-2000 | 2,000 | F14 or F16 | 55 / 46 | 46 | Ø60 | 50 | 46 |
| ATQ-2500 | 2,500 | F14 or F16 | 110 / 92 | 46 | Ø60 | 52 | 46 |
| ATQ-4000 | 4,000 | F16 / F25 | 150 / 125 | 46 | Ø60 | 104 | 73 |
| ATQ-6000 | 6,000 | F16 / F25 / F30 | 180 / 150 | 46 | Ø70 | 106 | 73 |
Sources: HYLINE-E and HYLINE-EQ data sheets, Advanced Actuators, August 2026. Images are representative. The final model number, certification and configuration are confirmed when you order.
3D model
Rotate and zoom a representative HYLINE-E, then switch to HYLINE-EQ in the explorer to compare the two.
The model only loads when you ask for it.
Valves and applications
Electric quarter-turn actuation for isolation and control duties, wherever there is power but no air or hydraulic supply.
Ball valvesButterfly valvesPlug valvesDampers
Hazardous area? HYLINE-EQ has an Ex d explosion-proof enclosure option. Tell us the zone, gas group and temperature class, and we will confirm the certification for your exact unit.
Not sure it is the right fit? With compressed air on site, see HYLINE-K rack and pinion. For high torque with spring-return fail-safe, see HYLINE-R.
On-off and modulating duties on utility and process lines, where an air supply is not practical.
HYLINE-EQ enclosures, heaters and over-torque protection for demanding process areas.
Isolation and control valves at treatment works and pumping stations.
Quarter-turn valves and dampers on auxiliary and balance-of-plant systems.
Sealed IP67 and IP68 enclosures for exposed locations.
Everyday automation of quarter-turn valves and dampers.
Certification
Certification depends on the specification, the components used and the area classification. Tell us what your project calls for and we will confirm the marks for your unit when we quote.









Downloads
Sizing help
Send the valve type, size and torque, the stem and flange, and your power supply, and we will come back with the right size and range.
Already installed
Overhaul, repair and spares for actuators in service, with commissioning support on site.
Size your HYLINE-E
We just need three details.
Replacing one? Send the model code from the nameplate and a photo, and we will work from those.
Type and size, its torque, and the stem and ISO 5211 flange if you have them.
Voltage and phase, and whether you need on-off, modulating or intelligent control.
Enclosure, ambient temperature and area classification.
Email us your detailsCall +44 (0)1535 655151
Prefer us to call you? Request a callback.
HYLINE-E suits general automation, with up to 1,200 starts per hour on modulating duty. HYLINE-EQ is built for heavy process duty, with a double worm gear, over-torque switches, a de-clutchable handwheel, more enclosure choices and fail-safe options. Both cover up to 6,000 Nm.
Add a safety factor of at least 20% to the valve torque and choose the first model whose output torque is above the new figure. Then check the stem connection and the ISO 5211 pattern match the valve.
The self-locking gear train holds the valve where it is. Where a valve must move on loss of power, HYLINE-EQ is available with battery backup or a spring-return module. On HYLINE-E, the response to a lost 4-20 mA or 2-10 V signal can be set to open or closed.
On-off with limit switches; modulating from a 4-20 mA signal (or 2-10 V on HYLINE-E) with matching feedback; and intelligent units with local controls and status indication. Fieldbus is available on request for HYLINE-EQ.
HYLINE-E: single phase 110 or 220 V AC, three phase 380 or 440 V AC, or 12, 24 or 48 V DC up to ATE-200. HYLINE-EQ: single phase 220 V AC and three phase 380 V AC as standard, with 110 V AC, 220 or 440 V AC three phase, 24 V AC and 24 V DC options.
Yes. HYLINE-E has a detachable crank handle as standard, with a handwheel option. HYLINE-EQ has a de-clutchable handwheel.
HYLINE-E: S2 30 minutes on on-off duty, and S4 40% with up to 1,200 starts per hour on modulating duty. HYLINE-EQ: S2 15 minutes at 380 V AC or 10 minutes at 220 V AC, and S4 25% with up to 600 starts per hour.
HYLINE-EQ has an Ex d explosion-proof enclosure option. Tell us the zone, gas group and temperature class, and we will confirm the certification for your exact unit before you order.