An electro-hydraulic valve actuator uses electrical control to produce hydraulic movement. Pressurised oil drives a cylinder or rotary mechanism, while electrical commands determine when and how the valve moves. In a self-contained package, a local electric motor, pump and reservoir provide the hydraulic supply.
This arrangement can be useful where a valve needs substantial thrust or torque and there is no suitable instrument-air or hydraulic network. It can also be specified for controlled positioning, isolation or shutdown duties, provided the complete package meets the application requirements.
Self-contained or supplied by a central power unit
An electro-hydraulic system does not always carry its own pump. Electrically operated control valves can direct oil from a central hydraulic power unit to the actuator. Where a hydraulic ring main already exists, that may be the appropriate arrangement.
A self-contained package places the hydraulic power source with the actuator. It reduces the external hydraulic distribution needed for that valve, while introducing a local motor, reservoir and controls to inspect and maintain. Shared electrical supplies and control systems can still affect several valves, even when their hydraulics are separate.
The parts of the package
| Part | Its job |
|---|---|
| Hydraulic cylinder or rotary mechanism | Converts fluid pressure into valve movement |
| Pump and motor, where fitted | Supply oil at the required flow and pressure |
| Reservoir | Accommodates the circuit’s fluid requirements |
| Control and holding valves | Direct, regulate or block flow according to the circuit design |
| Position feedback and controller | Measure position and control movement where required |
| Spring or accumulator, where specified | Store energy for movement following a defined failure |
The combination changes with the duty. A simple on-off package and a modulating package may share a mechanical actuator but require different controls.
Moving and holding the valve
For modulating service, the position controller compares a demand signal with measured position. It adjusts hydraulic flow until the actuator reaches the required position within the configured control band. On-off service instead requires movement between defined positions, with suitable confirmation.
Some self-contained designs stop the pump once the position is reached and use holding valves to restrict oil movement. Other systems maintain pressure or control flow differently. Low oil compressibility supports a stiff response, but holding accuracy also depends on leakage, temperature, external load and the mechanical linkage.
A change in indicated position does not automatically mean the actuator has moved. Feedback and linkage problems need to be distinguished from hydraulic drift.
What makes it fail safe
Fail-safe movement needs enough available energy and a functioning path for that energy to move the valve. A spring-return design can use stored spring energy; an accumulator arrangement uses stored hydraulic energy. The control circuit must release or direct that energy when the specified failure occurs.
Loss of command and loss of electrical power are different events. A controller can request a position following signal loss while power is available, but it cannot create mechanical energy after all supplies disappear. Likewise, double-acting operation alone does not guarantee that the valve will remain fixed. Our fail-safe guide explains the specification questions.
Power and speed need separate checks
A low standby demand can help a remote installation, but the supply must also support starting current and movement under load. A solar or battery system needs an energy calculation based on operating frequency, stroke energy, auxiliary loads and the required reserve.
Movement speed depends on the available flow, actuator displacement, load and control arrangement. Electronic response time is not valve stroke time. Ask for opening, closing and emergency times for the assembled valve and actuator under stated conditions.
HYLINE and local hydraulic power
HYLINE is our linear actuator platform for sliding-stem, globe and control valve duties. The published range covers 100 to 100,000 kgf of thrust and strokes up to 300 mm, with ring-main or self-contained hydraulic supply options. These are platform ranges; the required thrust, stroke, pressure and speed must be confirmed together for the selected build.
A HYFLOW pumping unit provides the local hydraulic source for a self-contained package. HYCONTROL positioning and HYTRACK feedback are available to suit the control requirement.
Information to include in an enquiry
Provide the valve’s torque or thrust data, allowable stem load, travel, opening and closing times, operating frequency and required failure responses. Add the electrical or hydraulic supply available, control signals, mounting details and environmental conditions.
For hazardous-area applications, include the complete area classification and project approval requirements so the exact equipment configuration can be checked. Contact our engineers to discuss the package.
Discuss your valve application
Contact our engineers to discuss your valve duty and application requirements.